MAzak QT20N - Thermal Trip

will_0000

Aluminum
Joined
Dec 16, 2012
Location
Great Britain
As is always the way started up our QT20N This afternoon to run a quick job and non of the hydraulics came on. the screen showed a 200 alarm - Thermal Trip (Emergency Stop) Some how I don't think it is a thermal issue as the machine has been cold for a couple of days.

Looking at the diagnostics page I get a couple of other alarms, are these an off shoot of the thermal alarm or causing the thermal alarm?

IMG_20170523_192229.jpg
IMG_20170523_192805.jpg

I have gone round all the breakers and reset them all but still the same issue.

What the book says:

200: Thermal relay for hydraulic unit head lubricating oil feed motor inside electric control panel has tripped.
204: Alarm had occurred in spindle controller
241: Cooling/chip conveyor motor thermal relay inside electric control panel has tripped. )Does this run on the same trip as 200?)
 
Thank you, benganboll your a genius! Traced the main incoming phases and one had come lose on an inner terminal,clamped it back up and off she ran.
 
for the record
"thermal trip" in Mazak speak is a tripped overload on a motor contactor.
alarms are top to bottom in importance.
a loose or missing phase will overdraw current on one leg which will trip an overload.
 








 