I picked up a 3 phase 220 to 600 volt transformer for a rotary phase converter.
The phase converter older and is capacitor start but does not have balance caps. I do plan to balance it in the future.
When I opened up the transformer I was very surprised to find it only had 2 transformer coils.
What I could find out about it is it is called an open delta transformer.

My question is, Will the unbalanced supply act the same through this transformer as with a transformer with 3 transformer coils.
or should I be looking for a new transformer.
Thanks
Mike
 
It should work fine if the transformer has enough capacity. I power my 575-V Aciera mill with an RPC feeding two 240-575 single phase transformers arranged open delta. No issues.


Sent from my iPhone using Tapatalk
 
Thank you for your reply.
The transformer nameplate size is 30 kva
the phase converter is 7.5 hp
I was not sure if this style of transformer would contribute to more phase imbalance.
Mike
 
No, it should not add to imbalance, except by the voltage boost ratio. My RPC is a well balanced commercial unit, so no issues running my CNC either with 240 -> 380V xformer.