300sniper

Hot Rolled
Joined
Nov 14, 2006
Location
Greenwood, Ca
I had this temped up at my old location but now I just moved. I am doing this permanent so I want to make sure it is right.

The machine is 67FLA (realistically, will never see that but that's what the tag is)
American Rotary 40HP AD rotary converter (have been using for almost a year)
125A breaker in the panel (had 150 before but I think this was technically to big for the RPC)
1/0 THHN to a safety 150 breaker/safety disconnect (I have this already)
1/0 THHN from disconnect to RPC
70A breaker on the RPC panel output (this has been working fine for almost a year)
4/2 SOOW from RPC breaker to machine

The disconnect and RPC are less than 10' from the machine. I want to make sure this all meets code. From the experts, does this sound correct?
 








 