Dmg NLX 2500, Mitsubishi M730BM Controls, parameter write problem
Close
Login to Your Account
Likes Likes:  0
Results 1 to 3 of 3
  1. #1
    Join Date
    Jan 2011
    Location
    telford, pa
    Posts
    359
    Post Thanks / Like
    Likes (Given)
    31
    Likes (Received)
    102

    Default Dmg NLX 2500, Mitsubishi M730BM Controls, parameter write problem

    Hello, my controls under "Settings " is sort of grayed out on the first line that says NC Parameter Write". The next line "Mapps parameter write" and down are usable. How do I get the option turned back on? Follow up question too, I am looking at the two corresponding user parameters that control the set up mode switch. Currently the set mode does not work. When you open the door nothing happens. Nor does the sign on the controls that says setting mode light up and the buzzer doesn't work. Any help would be greatly appreciated, thank you everyone.

  2. #2
    Join Date
    Dec 2014
    Country
    UNITED STATES
    State/Province
    New York
    Posts
    818
    Post Thanks / Like
    Likes (Given)
    299
    Likes (Received)
    195

    Default

    How long have you had this machine? Is this brand new?

  3. #3
    Join Date
    Jan 2006
    Location
    Portland, OR
    Posts
    133
    Post Thanks / Like
    Likes (Given)
    39
    Likes (Received)
    6

    Default

    Quote Originally Posted by james siffel View Post
    Hello, my controls under "Settings " is sort of grayed out on the first line that says NC Parameter Write". The next line "Mapps parameter write" and down are usable. How do I get the option turned back on? Follow up question too, I am looking at the two corresponding user parameters that control the set up mode switch. Currently the set mode does not work. When you open the door nothing happens. Nor does the sign on the controls that says setting mode light up and the buzzer doesn't work. Any help would be greatly appreciated, thank you everyone.
    In MDI mode go to setting page, type "PARAMETER" and hit input, the text will go away. You then should be able to go into settings page specifically (61 on my machine) and turn "NC Parameter write" to valid.


    I dont use the setting mode so unsure about that (this is on an NHX4000)

    spare door interlock keys come in handy


Tags for this Thread

Bookmarks

Posting Permissions

  • You may not post new threads