Haas Vf-2 on 100 Amp Panel, Phase Converter Recommendations - Page 2
Close
Login to Your Account
Page 2 of 2 FirstFirst 12
Results 21 to 30 of 30
  1. #21
    Join Date
    Aug 2007
    Country
    UNITED STATES
    State/Province
    Idaho
    Posts
    1,506
    Post Thanks / Like
    Likes (Given)
    213
    Likes (Received)
    483

    Default

    I changed the breaker for this and my own curoisity, It is still running fine, it is a 12k machine if that matters. I have 400 amps 242 volts here and am going to 200 amps at 213v in Idaho so I have power concerns as well. That compressor is a big horse to feed, you might put in a smaller one and let the big one pick up any slack by adjusting the pressure on the big one a bit lower, also it taked a lot more power to make 175 psi as many compressors as opposed to the 90 psi you actually need.

  2. #22
    Join Date
    Nov 2016
    Country
    UNITED STATES
    State/Province
    New York
    Posts
    116
    Post Thanks / Like
    Likes (Given)
    3
    Likes (Received)
    28

    Default

    Well its good to see I'm not the only one with the machine shut down problem. I run VF2ssyt on 20hp perfect phase and 150 amp service. If spindle ramps at same time as compressor fires up machine shuts down completely. Also, during rapid and ramp I sometimes get low voltage and machine is slowed down if I have heaters in my shop running. I noticed my machine runs about 97-98% voltage at stand still and drops down to 91% all the time during ramps so I changed the voltage configuration and machine sits at about 104% which is still within the Haas 10% tolerance and now it drops to mid and upper 90s when running and I haven't had low voltage or shut down since. I also bought a VFD and a 3 phase motor for my compressor so I could have much longer start up ramp and perhaps even run it slower for less noise, but have not got around to installing it yet since I haven't had shutdowns since.

  3. #23
    Join Date
    Nov 2019
    Country
    UNITED STATES
    State/Province
    Pennsylvania
    Posts
    17
    Post Thanks / Like
    Likes (Given)
    10
    Likes (Received)
    0

    Default

    Quote Originally Posted by kustomizer View Post
    I changed the breaker for this and my own curoisity, It is still running fine, it is a 12k machine if that matters. I have 400 amps 242 volts here and am going to 200 amps at 213v in Idaho so I have power concerns as well. That compressor is a big horse to feed, you might put in a smaller one and let the big one pick up any slack by adjusting the pressure on the big one a bit lower, also it taked a lot more power to make 175 psi as many compressors as opposed to the 90 psi you actually need.
    400 amps, so nice. The compressor is in the facility and it is running a 16 stage screen press (for the other tenant) so I will have to see how much psi/cfm he is actually using. I know it turns on every 20 minutes or so which could be frequent enough to turn on at the same time the machine is doing a high amp startup/operation. Thank you for the help on this and I hope your new power situation works out for you.

  4. #24
    Join Date
    Nov 2019
    Country
    UNITED STATES
    State/Province
    Pennsylvania
    Posts
    17
    Post Thanks / Like
    Likes (Given)
    10
    Likes (Received)
    0

    Default

    Quote Originally Posted by Lazyman View Post
    Well its good to see I'm not the only one with the machine shut down problem. I run VF2ssyt on 20hp perfect phase and 150 amp service. If spindle ramps at same time as compressor fires up machine shuts down completely. Also, during rapid and ramp I sometimes get low voltage and machine is slowed down if I have heaters in my shop running. I noticed my machine runs about 97-98% voltage at stand still and drops down to 91% all the time during ramps so I changed the voltage configuration and machine sits at about 104% which is still within the Haas 10% tolerance and now it drops to mid and upper 90s when running and I haven't had low voltage or shut down since. I also bought a VFD and a 3 phase motor for my compressor so I could have much longer start up ramp and perhaps even run it slower for less noise, but have not got around to installing it yet since I haven't had shutdowns since.
    Lazyman, are you adjusting the voltage in the Haas next-gen control itself?

  5. #25
    Join Date
    Nov 2016
    Country
    UNITED STATES
    State/Province
    New York
    Posts
    116
    Post Thanks / Like
    Likes (Given)
    3
    Likes (Received)
    28

    Default

    Quote Originally Posted by bjf5051 View Post
    Lazyman, are you adjusting the voltage in the Haas next-gen control itself?
    Not the control, the actual physical power connections in the electrical cabinet. I believe there are 3 positions to accommodate people with slightly lower or higher voltages. Have not had an issue so far no shut downs yet and have never seen machine rapid slow down due to low voltage like I would often get before when running shop heat and compressor.

  6. #26
    Join Date
    Nov 2016
    Country
    UNITED STATES
    State/Province
    New York
    Posts
    116
    Post Thanks / Like
    Likes (Given)
    3
    Likes (Received)
    28

    Default

    Quote Originally Posted by bjf5051 View Post
    Lazyman, are you adjusting the voltage in the Haas next-gen control itself?
    Not the control, the actual physical power connections in the electrical cabinet. I believe there are 3 positions to accommodate people with slightly lower or higher voltages. Have not had an issue so far no shut downs yet and have never seen machine rapid slow down due to low voltage like I would often get before when running shop heat and compressor.

  7. #27
    Join Date
    Nov 2019
    Country
    UNITED STATES
    State/Province
    Pennsylvania
    Posts
    17
    Post Thanks / Like
    Likes (Given)
    10
    Likes (Received)
    0

    Default

    Quote Originally Posted by Lazyman View Post
    Not the control, the actual physical power connections in the electrical cabinet. I believe there are 3 positions to accommodate people with slightly lower or higher voltages. Have not had an issue so far no shut downs yet and have never seen machine rapid slow down due to low voltage like I would often get before when running shop heat and compressor.
    Good to know thanks!

  8. #28
    Join Date
    Oct 2019
    Country
    UNITED STATES
    State/Province
    Texas
    Posts
    202
    Post Thanks / Like
    Likes (Given)
    21
    Likes (Received)
    26

    Default Haas incoming power, voltage selection physical settings

    Quote Originally Posted by bjf5051 View Post
    Good to know thanks!

    Haas incoming power, voltage selection physical settings. See attached picture and physically select 3-wire-set location by moving the 3 black wires (only) to selected location based on your general voltage readings. In my case I mated them with the 244V-360V yellow set of wires. leaving my pink, green and blue open.

    On a seperate note...
    Was told that the created 3phase leg (the high leg in my case) should be on L2, the center incoming lug on main switch. Whether that is true in everyones case or not I have no idea, in my case it was true and what got me up and running. Where before I had e-stop errors at rpm increase/decrease and delta/wye changes.

    -TH
    Attached Thumbnails Attached Thumbnails img_20191022_123556529.jpg  

  9. #29
    Join Date
    Jun 2020
    Country
    UNITED STATES
    State/Province
    California
    Posts
    32
    Post Thanks / Like
    Likes (Given)
    19
    Likes (Received)
    3

    Default 30 amp breaker on 3 phase? and on 220? or 440?

    Quote Originally Posted by kustomizer View Post
    Mine only shut down 2 times and while the spindle was ramping up, never during a cut. Other than that it ran as normal. I would think the PL4o would do you just fine. I put a 30 amp breaker this morning on my VF2SS 30hp today and ran all day with no issue but there are no tools larger than 7/8 dia on this job in 6061 though this is in California with 3 ph power. I think your compressor may be as much of the issue as the machine. A couple of 3hp compressors may help, especially if they don't need the phase converter.
    30 amp breaker on 3 phase? and on 220? or 440?

    Is your machine a 30hP model requireing 70 amps on 220 3phase?

  10. #30
    Join Date
    Aug 2007
    Country
    UNITED STATES
    State/Province
    Idaho
    Posts
    1,506
    Post Thanks / Like
    Likes (Given)
    213
    Likes (Received)
    483

    Default

    Quote Originally Posted by Gman4405 View Post
    30 amp breaker on 3 phase? and on 220? or 440?

    Is your machine a 30hP model requireing 70 amps on 220 3phase?
    Yes, 220 ( 2 legs 122, one 242, 242 across any pair ), I was doing a test prior to moving a machine into a pole barn with 100amp single phase and wanted to know how small of a RPC I would need to buy for a temp situation. I had already ordered the power upgrade but it was going to take several months to complete ( it is done now ). I ran 3 months with the American rotary pl25, I had one shutdown caused by a blink in the power from a thunderstorm and one other time for an unknown reason. I have 8 machines here now and have run as many as 3 at a time, each on a 40 amp breakers along with a 3hp compressor, belt sanders, etc on 200 amps 208 3 phase.