    Hi,
    I am going to install vfd with fan motor ( rated 110kW) by replacing damper but VFD rating (that is readily available) is about 250kW. What Problems I will face after this oversizing?

  2. #2
    Join Date
    Feb 2018
    Country
    SWITZERLAND
    Posts
    10
    Post Thanks / Like
    Likes (Given)
    0
    Likes (Received)
    1

    Default

    No problems..

  3. Likes Murf liked this post
  4. #3
    Join Date
    Mar 2009
    Location
    Eureka, CA
    Posts
    3,787
    Post Thanks / Like
    Likes (Given)
    763
    Likes (Received)
    1320

    Default

    No problems as long as the larger VFD has O/L programming parameters that allow it to be dialed down (FLA) to the smaller load.


    Stuart

  5. #4
    Join Date
    Feb 2005
    Location
    Akron, OH
    Posts
    1,864
    Post Thanks / Like
    Likes (Given)
    289
    Likes (Received)
    1397

    Default

    Are you sure you mean kW? That's about 150 horsepower for your current one and 300 for your new one.