    Default Brown & Sharpe #2 surface grinder really 2 phase ?

    Well I just picked one up from a sale. Looking at machine label I see "2 phase".
    Strange.
    On the old GE motor label "2 phase".
    I've never heard of this before.
    I normally run 3 phase machines off a VFD as I only have single phase.
    Can I run this off a VFD, does anyone know ?
    Or any other ideas, please.
    Thanks,
    Bob

  2. #2
    Join Date
    Jul 2001
    Country
    UNITED STATES
    State/Province
    North Carolina
    Posts
    2,227
    Post Thanks / Like
    Likes (Given)
    261
    Likes (Received)
    558

    Default

    Niagara Falls supplied it to Buffalo.
    25Hz too.
    Add a start cap and a current relay.
    Most single phase cap start motors are
    really 90° 2 phase motors. Surprise !

    --Doozer

  3. Likes reggie_obe, sfriedberg liked this post
  4. #3
    Join Date
    Dec 2000
    Country
    UNITED STATES
    State/Province
    South Carolina
    Posts
    51,773
    Post Thanks / Like
    Likes (Given)
    3198
    Likes (Received)
    6045

    Default

    Philadelphia used to supply 2 phase to industry.

  5. #4
    Join Date
    Aug 2015
    Country
    UNITED STATES
    State/Province
    Illinois
    Posts
    1,736
    Post Thanks / Like
    Likes (Given)
    1343
    Likes (Received)
    743

    Default

    If it is the old style with a serpentine flat belt your best bet is a motor swap.

  6. #5
    Join Date
    Jul 2004
    Location
    Reddington, N.J., U.S.A.
    Posts
    3,694
    Post Thanks / Like
    Likes (Given)
    744
    Likes (Received)
    471

    Default

    What Doozer said, trivial to run a two phase motor on single phase 220vac.
    Don't swap out the motor.

    Where was the shop that this machine came from?

  7. #6
    Join Date
    Nov 2017
    Country
    UNITED STATES
    State/Province
    South Carolina
    Posts
    140
    Post Thanks / Like
    Likes (Given)
    31
    Likes (Received)
    31

    Default

    The machine came from Reading PA.
    The shop has 430 volt supply and they used a transformer, down to 230 volts.
    I didn't realize it was a 2 phase motor when I picked it up.

    I'm not getting what you guys are saying about running motor off 230 volts single phase.
    Could somebody spell it out for me, please ?

  8. #7
    Join Date
    Jun 2001
    Location
    St Louis
    Posts
    19,544
    Post Thanks / Like
    Likes (Given)
    2476
    Likes (Received)
    3736

    Default

    If you want to enough, or happen to have the transformers laying around, you can hook up the classic "Scott" connection and give it 2 phase power.

    Be the only one in town with real 2 phase power!

  9. #8
    Join Date
    Dec 2010
    Country
    UNITED STATES
    State/Province
    Pennsylvania
    Posts
    2,351
    Post Thanks / Like
    Likes (Given)
    39
    Likes (Received)
    329

    Default

    For Scott connection you will need 3 phase. 2 phase power was used quite a bit in the big cities. I lived in NJ and many machines that came from Paterson, Newark, NYC and many others as well as those mentioned had 2 phase motors. At one time 2 phase motor were all over the place now they are hard to find. I did get them to run on single phase with an RPC but been so long I don't remember how. As mentioned previously your best way is to swap the motor with a single phase motor if it's belt drive. 2 phase is a 4 wire motor, you will need 4 wire supply. VFD has only 3.
    Last edited by Froneck; 09-24-2021 at 06:18 AM.

  10. Likes Overland liked this post
  11. #9
    Join Date
    Nov 2017
    Country
    UNITED STATES
    State/Province
    South Carolina
    Posts
    140
    Post Thanks / Like
    Likes (Given)
    31
    Likes (Received)
    31

    Default

    Reggae,
    I tried to Google running 2 phase motor off single, but no useful results.
    Could you spell out for me what you're saying with capacitors and so on please ?
    Bob

  12. #10
    Join Date
    Jul 2004
    Location
    Reddington, N.J., U.S.A.
    Posts
    3,694
    Post Thanks / Like
    Likes (Given)
    744
    Likes (Received)
    471

    Default

    Quote Originally Posted by Overland View Post
    Reggae,
    I tried to Google running 2 phase motor off single, but no useful results.
    Could you spell out for me what you're saying with capacitors and so on please ?
    Bob
    I will have to check my one and only 2ph machine and get back to you. At work now.
    There are also some previous discussions and solutions posted here. Might be able to provide that more quickly.

  13. #11
    Join Date
    Jul 2004
    Location
    Reddington, N.J., U.S.A.
    Posts
    3,694
    Post Thanks / Like
    Likes (Given)
    744
    Likes (Received)
    471

    Default

    An old thread on 2 phase: Single to 2 phase conversion

    This thread is where I originally gleaned my information from: 2 phase converter??????
    See post #7, I'll double check, but I'm running it as diagrammed using just a run cap. on the other phase, no potential relay, start button, etc.

  14. Likes Overland liked this post
  15. #12
    Join Date
    May 2020
    Country
    UNITED STATES
    State/Province
    Minnesota
    Posts
    535
    Post Thanks / Like
    Likes (Given)
    212
    Likes (Received)
    225

    Default

    VFD and a Scott-T transformer arrangement if the motor has historical/antique/aesthetic value for a home shop installation. Otherwise swap it.

  16. #13
    Join Date
    Nov 2017
    Country
    UNITED STATES
    State/Province
    South Carolina
    Posts
    140
    Post Thanks / Like
    Likes (Given)
    31
    Likes (Received)
    31

    Default

    Thanks Reggie

  17. #14
    Join Date
    Jul 2004
    Location
    Reddington, N.J., U.S.A.
    Posts
    3,694
    Post Thanks / Like
    Likes (Given)
    744
    Likes (Received)
    471

    Default

    Quote Originally Posted by Just a Sparky View Post
    VFD and a Scott-T transformer arrangement if the motor has historical/antique/aesthetic value for a home shop installation. Otherwise swap it.
    No, there is no need.
    Scott-T transformers aren't cheap although it's been explained that you can you use a simple center tapped and get "close".
    This is for a surface grinder, can't substitute any old wash machine motor and be fine.

  18. #15
    Join Date
    Jun 2001
    Location
    St Louis
    Posts
    19,544
    Post Thanks / Like
    Likes (Given)
    2476
    Likes (Received)
    3736

    Default

    [QUOTE=Froneck;3815949........................ 2 phase is a 4 wire motor, you will need 4 wire supply. VFD has only 3.[/QUOTE]

    Motor has two coil sets, but can be wired 3 or 4 wire, usually, depending on what you have available as a source. Either way it is still 90 deg phase difference.

    A 3 wire motor is harder to use with 4 wire power than the 4 wire motor is to set up for 3 wire.

    VFD by itself is not much help since it produces 3 phase unless reprogrammed significantly.

  19. #16
    Join Date
    Dec 2010
    Country
    UNITED STATES
    State/Province
    Pennsylvania
    Posts
    2,351
    Post Thanks / Like
    Likes (Given)
    39
    Likes (Received)
    329

    Default

    Yes I know 2 phase motors have 2 soil sets yes 2 can be commoner, I do remembering connecting wires together when I adapted 2 phase motors to on on single phase power. Was about 50 years ago. Kinda forgot what I did! Machinery was really cheap when on auction they were found to have 2 phase motors and where I lived NYC and Philadelphia were about the same distance, little over hour drive. Dealers stayed away from 2 phase machinery as well as the average shop owner. I could get them cheap and sell them to guys with small shops though I don't remember converting any that had larger than 10HP motors. From what I have read Tesla's first few 2 phase alternators were actually 2 single phase Alternators coupled 90° apart.