I am in the process of getting a 480v 3ph service installed on a shop property. I told the electrician doing the work that I wanted to step back down to 240/120, and re-feed the existing 240/120 1ph panels from that.
They dropped off the transformer two days ago and it is 480v to 208y/120. He basically brushed it off as not a big deal, and said he wasn't sure he could get one in 240v with a neutral tap. I don't seem to have much trouble finding a 75kva 480 to 240/120 transformer.
Should I be okay living with having 208 in this building now, or make them get me the 240v transformer that I originally requested. (And that they referenced on the quote)
I have a suspicion that the 208 transformer was cheaper...but maybe that is just the skeptic in me.
Any input is appreciated, thanks.