Isolation Transformer Wiring Help Needed
Close
Login to Your Account
Likes Likes:  0
Results 1 to 4 of 4
  1. #1
    Join Date
    Aug 2004
    Location
    Ohio, USA
    Posts
    2,120
    Post Thanks / Like
    Likes (Given)
    311
    Likes (Received)
    110

    Default Isolation Transformer Wiring Help Needed

    I have a GE QL series drive isolation transformer I'm looking to use with a phase perfect. I'm a little confused in regards to wiring it up...I believe H1, H2, H3 are for my Delta power input. Are X0, X1, X2, and X3 my Wye outputs, or is it Y0, Y1, Y2 and Y3? Why does it appear that there are 2 Wye output taps?

    img_6735.jpg

    img_6736.jpg

  2. #2
    Join Date
    Jul 2014
    Location
    MI USA
    Posts
    884
    Post Thanks / Like
    Likes (Given)
    197
    Likes (Received)
    367

    Default GE Drive Isolation Multitap Xformer

    Your Model was a special made around 2005. It does have two Wye output windings as indicated on the tag.
    X's are 460/266V @ 20KVA capacity, Y's are 230/133V @ 7.5KVA

    xformoutputcapacity.jpg

    A similar but not exact connection diagram, Yours has the two Wye output windings.

    ge-drivexformtaps.jpg

    SAF Ω

  3. #3
    Join Date
    Jul 2008
    Location
    Philadelphia
    Posts
    1,942
    Post Thanks / Like
    Likes (Given)
    514
    Likes (Received)
    445

    Default

    FWIW be aware that XO shown on the star or wye config may not be accessible on the xformer, like on a 3 phase dual voltage AC induction motor.
    The fact that you are lucky enough to have a schematic of sorts and numbered wires. I would still ohm the thing out, just to be sure all is okay and the smoke that makes all electrical devices work won't be let out.

  4. #4
    Join Date
    Jun 2006
    Location
    San Jose, CA
    Posts
    582
    Post Thanks / Like
    Likes (Given)
    495
    Likes (Received)
    55

    Default

    Quote Originally Posted by Machinery_E View Post
    I have a GE QL series drive isolation transformer I'm looking to use with a phase perfect. I'm a little confused in regards to wiring it up...I believe H1, H2, H3 are for my Delta power input. Are X0, X1, X2, and X3 my Wye outputs, or is it Y0, Y1, Y2 and Y3? Why does it appear that there are 2 Wye output taps?

    img_6735.jpg

    img_6736.jpg
    Can you take some clearer/better pictures of the terminal bars?
    It’s really hard to read them.