    Default Question about remote controls on Teco L510

    We're putting a VFD on our mill and I'm a little lost in the details with one particular part of the setup, maybe someone more familiar can help. This is the VFD: https://www.tecowestinghouse.com/Man...ion_manual.pdf
    On our remote controls I would like to have the following:

    JOG FWD / JOG REV (either momentary pushbuttons or a momentary return to center paddle switch
    START FWD / START REV (again there's a few ways to do this, my preference is with a return to center momentary paddle)
    STOP
    E-STOP

    Conveniently the L510 has a pretty good logic board and can do all of this with simple inputs, no extra relays or switches. HOWEVER there are only 5 total 'multi-function terminals' despite there being something like 20 options for them. I can wire the JOG FWD/JOG REV/FWD/REV/STOP using these terminals and I can also wire the E-stop using these terminals but I'm short a terminal to do both at once. I could of course give up the separate STOP / E-STOP buttons and have a single sustained switch but for a few reasons I prefer both, mainly because I think that an E-STOP should be just that, an emergency stop. Is there another way to wire an E-STOP into these inverters which still uses the internal logic board to electrically brake the machine? I know I could wire in a relay to physically cut power but with the loss of electric braking this "emergency" stop would be slower than the normal stop button.
    I know I could redesign my switching a little to free up a terminal and I may have to do that but my question first is whether there's a way that I'm not seeing to hook up a dedicated e-stop which uses the VFD's accelerated stopping but doesn't need to be run off of one of the multi-function terminals (S1-S5).

  2. #2
    Join Date
    Aug 2010
    Location
    Tucson, AZ
    Posts
    251
    Post Thanks / Like
    Likes (Given)
    8
    Likes (Received)
    64

    Default

    Just have the E-Stop interrupt the COM connection to kill all run controls if you want the VFD's braking to stay active. Alternative would be to use 2 wire control with a latching relay for forward and reverse, this requires an alternate power source for the relay power and momentary For/Rev buttons for run. Stop button breaks the power to the relays/latch. You loose power the latch also releases. Simple setup. This gives you 1 extra input, the E-Stop would then break power to the latching relays and issue a rapid stop command to the VFD.

  3. #3
    Join Date
    Oct 2008
    Location
    Central Ohio, USA
    Posts
    1,961
    Post Thanks / Like
    Likes (Given)
    842
    Likes (Received)
    566

    Default

    I spent the day working on the new shop and I'm spent. Does this example from a Teco N3 help?

    example.jpg

  4. #4
    Join Date
    Jul 2011
    Location
    New Orleans
    Posts
    46
    Post Thanks / Like
    Likes (Given)
    1
    Likes (Received)
    3

    Default

    Quote Originally Posted by Ohio Mike View Post
    I spent the day working on the new shop and I'm spent. Does this example from a Teco N3 help?

    example.jpg

    Thanks, that's a little easier to read than what I had in the manual. I think I have it figured out now.

  5. Likes Ohio Mike liked this post
  6. #5
    Join Date
    Jul 2011
    Location
    New Orleans
    Posts
    46
    Post Thanks / Like
    Likes (Given)
    1
    Likes (Received)
    3

    Default

    Quote Originally Posted by mksj View Post
    Just have the E-Stop interrupt the COM connection to kill all run controls if you want the VFD's braking to stay active. Alternative would be to use 2 wire control with a latching relay for forward and reverse, this requires an alternate power source for the relay power and momentary For/Rev buttons for run. Stop button breaks the power to the relays/latch. You loose power the latch also releases. Simple setup. This gives you 1 extra input, the E-Stop would then break power to the latching relays and issue a rapid stop command to the VFD.
    Thank you. I knew there was a simple solution I just got bogged down in that PDF. They don't even send an actual manual with the unit anymore it's just an install guide! Anyway, breaking COM is exactly what I was looking for, that gives me the separate e-stop button and operating stop button that I wanted. The latching relay is great too, I was considering a VFD reset button on the controls but it seems like these units are reliable enough that there's no real need. Good to know I can free up another input if I need to.

  7. #6
    Join Date
    Feb 2004
    Location
    peekskill, NY
    Posts
    25,122
    Post Thanks / Like
    Likes (Given)
    0
    Likes (Received)
    5033

    Default

    Quote Originally Posted by calderp View Post
    Thank you. I knew there was a simple solution I just got bogged down in that PDF. They don't even send an actual manual with the unit anymore it's just an install guide! .
    Actually that's a sign they are learning. Used to be, they sent a paper manual and that was missing some key information.