teco 1hp 230v VFD starts backwards and slow
Close
Login to Your Account
Results 1 to 15 of 15
  1. #1
    Join Date
    Apr 2007
    Location
    cincinnati, ohio
    Posts
    85
    Post Thanks / Like
    Likes (Given)
    0
    Likes (Received)
    7

    Default teco 1hp 230v VFD starts backwards and slow

    Hi gentlemen

    I have an older Teco 1hp VFD 230 single phase to 230v three phase VFD. I had been using this VFD with a 3/4 horse motor with no problems. I upgraded to a 1 hp motor and I have a problem that I can't figure out and don't understand. When I attempt to start the motor at any frequency, it turns slowly in the wrong direction most of the time. Sometimes but rarely it will start and come up to speed in the correct or reverse direction. I have looked at all settings and can not solve the problem. Can you make any recommendations please so it will start in the correct direction as it used to when connected to the 3/4 hp motor? Both of the motors are GE 3 phase motors and are wired correctly. I have tried re-arranging all three phase lines with no change in the outcome. The only item I changed was the motor. When it does start up and run at the correct speed it performs properly, a variable speed, sufficient power no weird noises and no smoke escaping.

    Here is what the unit is

    1 HP, 230 Volts, 1 Phase, IP 20, Teco, JNEV-201-H1 MODEL #: JNEV-201-H1
    230 Volts 1 Phase Input, 230 Volts 3 Phase Output
    Bill
    Last edited by Mr_Bill; 01-08-2019 at 10:41 PM. Reason: add more details

  2. #2
    Join Date
    Jun 2012
    Location
    Eastern PA
    Posts
    844
    Post Thanks / Like
    Likes (Given)
    187
    Likes (Received)
    347

    Default

    Bill:

    If you swap any 2 of the phases at the output of the VFD(or at the motor) the direction should be reversed.

  3. Likes Steven-Canada liked this post
  4. #3
    Join Date
    Oct 2012
    Country
    UNITED STATES
    State/Province
    Iowa
    Posts
    303
    Post Thanks / Like
    Likes (Given)
    141
    Likes (Received)
    77

    Default

    There is a programing parameter in the VFD for motor size, is this set to 1HP?
    Running slow, are you sure the motor is not wired for 440VAC operation?

  5. #4
    Join Date
    Jul 2014
    Location
    MI USA
    Posts
    816
    Post Thanks / Like
    Likes (Given)
    193
    Likes (Received)
    341

    Default

    Post the nameplate tag of the motor.

    Is the motor starting unloaded?

    What is the motor's load?

    SAF Ω

  6. #5
    Join Date
    Jun 2001
    Location
    St Louis
    Posts
    17,469
    Post Thanks / Like
    Likes (Given)
    1619
    Likes (Received)
    2800

    Default

    Starting poorly suggests that one phase wire is not reliably connected, or the motor has an issue, or the VFD has an issue...

    A 3 phase motor should start easily and in the same direction every time. If it does not, it is either not getting 3 phase, one of its wires is not connected, or it has an internal problem.

    Many 1 HP motors have a thermal protector. Those things are not immortal, they can go bad. Could be the case. An ohmmeter check should give an answer to that question.

    My very first check would be to try that VFD with another motor. If it runs the other motor OK, then the one you are now trying to use is suspect.

  7. #6
    Join Date
    Mar 2009
    Country
    UNITED STATES
    State/Province
    California
    Posts
    4,534
    Post Thanks / Like
    Likes (Given)
    82
    Likes (Received)
    796

    Default

    Auto tune with the 1hp motor. While doing this chant "Teco is not cheapo" while sitting in the Lotus position.

  8. #7
    Join Date
    Aug 2004
    Location
    San Ramon, CA USA
    Posts
    2,598
    Post Thanks / Like
    Likes (Given)
    23
    Likes (Received)
    568

    Default

    Quote Originally Posted by JST View Post
    Starting poorly suggests that one phase wire is not reliably connected, or the motor has an issue, or the VFD has an issue...

    A 3 phase motor should start easily and in the same direction every time. If it does not, it is either not getting 3 phase, one of its wires is not connected, or it has an internal problem.

    Many 1 HP motors have a thermal protector. Those things are not immortal, they can go bad. Could be the case. An ohmmeter check should give an answer to that question.

    My very first check would be to try that VFD with another motor. If it runs the other motor OK, then the one you are now trying to use is suspect.
    Most failures inside of the VFD that might cause this would be showing up as a fault code. I like the idea of a bad connection or a thermal protector in the motor that is not working right. That would explain why it sometimes runs correctly. When you get a partial connection on one phase inside of the motor, it can spin in somewhat random directions.

  9. #8
    Join Date
    Apr 2007
    Location
    cincinnati, ohio
    Posts
    85
    Post Thanks / Like
    Likes (Given)
    0
    Likes (Received)
    7

    Default

    Quote Originally Posted by awander View Post
    Bill:

    If you swap any 2 of the phases at the output of the VFD(or at the motor) the direction should be reversed.
    Ok but the problem is that it is running slow like 50 rpm

  10. #9
    Join Date
    Aug 2004
    Location
    San Ramon, CA USA
    Posts
    2,598
    Post Thanks / Like
    Likes (Given)
    23
    Likes (Received)
    568

    Default

    Hook the drive back up to the old motor. If it runs that motor fine, it's the motor or wiring.

    Re: Autotuning: normally I would agree with that approach, but that particular Teco drive is basically a V/Hz drive with an automatic voltage boost at low speeds, it's not really a Sensorless Vector Drive (even though they say so). There is no tuning parameter for it, which is how you can tell...

  11. #10
    Join Date
    Apr 2007
    Location
    cincinnati, ohio
    Posts
    85
    Post Thanks / Like
    Likes (Given)
    0
    Likes (Received)
    7

    Default

    Quote Originally Posted by ignator View Post
    There is a programing parameter in the VFD for motor size, is this set to 1HP?
    Running slow, are you sure the motor is not wired for 440VAC operation?
    yes Motor is wired for 220 not 440

  12. #11
    Join Date
    Oct 2017
    Country
    UNITED STATES
    State/Province
    California
    Posts
    392
    Post Thanks / Like
    Likes (Given)
    106
    Likes (Received)
    99

    Default

    That sounds exactly like a three phase motor trying to start on single phase or with a very weak third leg.

    Disconnect one leg and briefly run the motor (be sure to isolate that wire, it will still develop a nasty voltage). Do that with each leg. I suspect once you will see no change in behavior and twice you will see no motor movement at all, or very, very little.

    If the above is true, wire the VFD back to the old motor. If the old motor works fine, then the VFD is fine and your other motor is wired wrong or burnt out.

  13. #12
    Join Date
    Mar 2009
    Country
    UNITED STATES
    State/Province
    California
    Posts
    4,534
    Post Thanks / Like
    Likes (Given)
    82
    Likes (Received)
    796

    Default

    Or the drive cannot handle a 1 hp motor. Even though the manual or drive name plate says 1Hp. Doesn't make it so on a ChiComm product.

  14. #13
    Join Date
    Aug 2004
    Location
    San Ramon, CA USA
    Posts
    2,598
    Post Thanks / Like
    Likes (Given)
    23
    Likes (Received)
    568

    Default

    Quote Originally Posted by rons View Post
    Or the drive cannot handle a 1 hp motor. Even though the manual or drive name plate says 1Hp. Doesn't make it so on a ChiComm product.
    But that would not make it try to spin the wrong direction...

  15. #14
    Join Date
    Mar 2009
    Country
    UNITED STATES
    State/Province
    California
    Posts
    4,534
    Post Thanks / Like
    Likes (Given)
    82
    Likes (Received)
    796

    Default

    Quote Originally Posted by Jraef View Post
    But that would not make it try to spin the wrong direction...
    You can't be sure what the feedback loop/recovery software is doing.

  16. #15
    Join Date
    Apr 2007
    Location
    cincinnati, ohio
    Posts
    85
    Post Thanks / Like
    Likes (Given)
    0
    Likes (Received)
    7

    Default

    I wanted to thank everyone for their input. This caused me to take another look at all the possible settings in the VFD. I didn't think that it would be that different with the 1/4 hp increase but evidently, it did. I updated the settings from F43 to F50 and that has solved the problem. It now starts good and runs great. It even starts at slow, mid and high RPMs forward and reverse. There were some good suggestions and ideas that I hadn't thought about. Again Thanks