Wired rpc to 600 transformer.......... Issues

windsormw

Aluminum
Joined
Dec 11, 2006
Location
The corner of Hill & William
Hello Pm

I have a Finch Williams rpc, built it myself and recently wired a 15 kva 240\600 transformer.

The hook up seemed straight forward but perhaps I've over looked something. I wired T1, T2 & T3 from rpc to X1, X2 & X3 on the transformer.

Any suggestions?
 

Attachments

  • 1445808429844.jpg
    1445808429844.jpg
    89.2 KB · Views: 183
  • 1445810056445.jpg
    1445810056445.jpg
    93.2 KB · Views: 235
  • 1445808368418.jpg
    1445808368418.jpg
    91.5 KB · Views: 189
  • 1445808322854.jpg
    1445808322854.jpg
    92.3 KB · Views: 193
So, what is the size of the RPC in kVA / HP?

WHAT will not build rpms? The RPC? You do not want a load on the RPC until you have it started up. If you are trying to start it with that in place, it won't work. Connect the transformer after the RPC is going.
 
It's 10 HP. No machines are on during start up. My rpc has worked fine for years.

Are you saying the transformer is drawing a big enough load to prevent the rpc from starting and closing a set of contacts after start up is the way to solve it?
 
Start the RPC and allow to come up to speed . . .

Wait 3 - 5 seconds

Close contactor between RPC and transformer (240V) and allow RPC speed to stabilize

Wait 1 second or more

Close contactor to load (600V)
 
I used a similar setup for several years before we moved into a building with a 400kVA 480V 3-phase service.

We designed a 2 lane log bucking line with 4 positioning conveyors each at 50HP and were able to power this drive cabinet (200HP of drives) and spin motors to rated speed with a 5HP RPC feeding a 15kVA 240:480 transformer . . . we couldn't accelerate the motors very fast but we could run them all and test all of our software all from this dinky little 5HP RPC and transformer combo.
 
Good. Should work OK then.

One serious issue is that the transformer, if not disconnected, is a load on the STARTING circuit..... And that may be most of the issue here. The start circuit may not be able to function with that transformer loading it un-necessarily.
 
Disconnect the starting circuit stuff.

Start the idler with a pony motor, unloaded. Then energize the
idler, then put the transformer online after the idler is up to
speed and the output is stable.

If the idler won't keep running after the pony motor is
removed, somethings wrong with the idler.

If the idler chokes and spins down when the transformer is
put online, there's something wrong with the transformer setup.
 
Scott, I have a 15 hp RPC coupled to a 15 kVA 240:600v autotransformer to run a 10 hp 600v planer.

As note above, I start the RPC in a no load configuration then close the fused disconnect to power up the transformer, and then start the planer. Works like a charm.

Suspect that all you require is a disconnect between the RPC and transformer.
 








 