    Hello, this might seem like a dumb question but I don't want to damage my VFD....Most instructions are for 220v wiring, I purchased a 110v Hyunyang VFD and a 110v 2.2kw spindle.. How do I wire the 110v to R,S,T, terminals?

  2. #2
    Join Date
    Mar 2009
    Country
    UNITED STATES
    State/Province
    California
    Posts
    5,172
    Post Thanks / Like
    Likes (Given)
    97
    Likes (Received)
    953

    Default

    Why is that VFD brand treated so disrespectfully?

    dad.jpg.jpg

    Before your post is locked, where is the link to the VFD manual?

  3. #3
    Join Date
    Oct 2012
    Country
    UNITED STATES
    State/Province
    Iowa
    Posts
    303
    Post Thanks / Like
    Likes (Given)
    145
    Likes (Received)
    77

    Default

    Quote Originally Posted by jstef View Post
    Hello, this might seem like a dumb question but I don't want to damage my VFD....Most instructions are for 220v wiring, I purchased a 110v Hyunyang VFD and a 110v 2.2kw spindle.. How do I wire the 110v to R,S,T, terminals?
    I was not aware that Hyunhyang manufactured a 120volt input VFD. Can you provide the model number you purchased.
    If it is a 120 input model, there would be a wiring diagram for this. But when you state 2.2Kw, that's 3HP, and I don't see 120V input models of any manufacture that is greater then 3/4HP motor size.
    I believe you need to wire your system with 240V input for this large a HP motor.

    EDIT, I see these are on eBay. And the motor is 110V rated, which is not the normal VFD I'm aware of that uses 120 input, and has a voltage doubler to produce power for a 240VAC 3 phase motor.
    The manual must have a diagram for 120 input 120 output.

  4. #4
    Join Date
    Jan 2007
    Location
    NY State
    Posts
    24
    Post Thanks / Like
    Likes (Given)
    1
    Likes (Received)
    1

    Default

    The spindle itself is 110volts also. The manual only covers connection for 220v, manual covers many different models. Spindle says 110v 8.5 amps. VFD model HY02D211B, input ac110v, output 3ph 110v, 20 amps, 2,2kw

    Joe

  5. #5
    Join Date
    Aug 2012
    Location
    California, Central Coast
    Posts
    3,798
    Post Thanks / Like
    Likes (Given)
    2199
    Likes (Received)
    1498

    Default

    This might help:
    Huanyang VFDs.... Banned from discussion
    I mean help it get to the bin faster.

  6. #6
    Join Date
    Aug 2010
    Location
    Tucson, AZ
    Posts
    229
    Post Thanks / Like
    Likes (Given)
    6
    Likes (Received)
    56

    Default

    Connect to any of the two input terminals per the description for the HY02D211B. Based on the output current you would need a 30-40A 120V input connection/breaker. The input is based on the VFD rating and not the load rating.

  7. #7
    Join Date
    Jan 2007
    Location
    NY State
    Posts
    24
    Post Thanks / Like
    Likes (Given)
    1
    Likes (Received)
    1

    Default

    wow, ok that sucks

  8. #8
    Join Date
    Sep 2011
    Country
    UNITED STATES
    State/Province
    Virginia
    Posts
    27,777
    Post Thanks / Like
    Likes (Given)
    7561
    Likes (Received)
    8635

    Default

    Quote Originally Posted by ignator View Post
    and I don't see 120V input models of any manufacture that is greater then 3/4HP motor size.
    Weg, Brazil made them. I had one, new with Warranty. Galco sourced and 2 HP IIRC.

    I'm sure they have competition, though I'm less sure "why" since 120 OR 240 VAC input units also exist, and some of them are even "doubler" capable to side-step need of a transformer.

    Mine was only for fast testing of basic integrity of used 3-P motors where only a long extension cord could be had for power source. Or an inverter off the motorcar's 12V system.

    It didn't have to spin them up to full gallop - just beat all Hell out of messing with meter readings, time-wise.

  9. #9
    Join Date
    Jun 2001
    Location
    St Louis
    Posts
    18,039
    Post Thanks / Like
    Likes (Given)
    1892
    Likes (Received)
    3044

    Default

    Well you just had to mention that name.... I'm tired of supporting those dang things.

    Yep it's gonna be thread locky-poo now.