gernoff
Hot Rolled
- Joined
- Mar 19, 2011
- Location
- Great Falls, Montana
I have a Yaskawa UAASKA-06CA1 spindle motor I need to control. The nameplate current is rated at 29A continuous and 39A for 30 minutes. The actual power rating of the motor is 3.7kw cont and 5.5kw for 30 min. In my googling I have seen comments that the high current spec is due to the 200v rating of the motor.
The question is: Although the motor current is shown as 29A cont / 39A max will I have any problem driving the motor with a 5.5kw VFD rated to 25A continuous (DuraPluse GS3)
I assume the downside is that I will simply not be able to drive the motor to its full rated power?
The VFD will be able to protect itself since it detects current etc. correct?
Thanks for the information.
The question is: Although the motor current is shown as 29A cont / 39A max will I have any problem driving the motor with a 5.5kw VFD rated to 25A continuous (DuraPluse GS3)
I assume the downside is that I will simply not be able to drive the motor to its full rated power?
The VFD will be able to protect itself since it detects current etc. correct?
Thanks for the information.